UTICA BOILERS JE Installation Manual Page 12

  • Download
  • Add to my manuals
  • Print
  • Page
    / 36
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 11
12
Removing Existing Boiler From Common Venting
System
When existing boiler is removed from common venting
system, common venting system is likely to be too large for
proper venting of appliances remaining connected to it.
At time of removal of existing boiler, following steps shall
be followed with each appliance remaining connected to
common venting system placed in operation, while other
appliances remaining connected to common venting system
are not in operation.
1.
Seal any unused openings in the common venting
system.
2.
Visually inspect the venting system for proper size and
horizontal pitch and determine there is no blockage or
restriction, leakage, corrosion and other deciencies which
could cause an unsafe condition.
3.
Insofar as is practical, close all building doors and
windows and all doors between the space in which the
appliances remaining connected to the common venting
system are located and other spaces of the building.
Turn on clothes dryers and any appliance not connected
to the common venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so
they will operate at maximum speed. Do not operate a
summer exhaust fan. Close replace dampers.
4.
Place in operation the appliance being inspected. Follow
the lighting instructions. Adjust thermostat so appliance
will operate continuously.
5.
Test for spillage at the draft hood relief opening after
5 minutes of main burner operation. Use the ame of
a match or candle, or smoke from a cigarette, cigar or
pipe.
6.
After it has been determined that each appliance remaining
connected to the common venting system properly vents
when tested as outlined above, return doors, windows,
exhaust fans, replace dampers and any other gas-burning
appliance to their previous conditions of use.
7.
Any improper operation of the common venting system
should be corrected so the installation conforms with
the National Fuel Gas Code, ANSI Z223.1/NFPA 54.
When resizing any portion of the common venting
system, the common venting system should be resized
to approach the minimum size as determined using the
appropriate tables in Chapter 13 of the National Fuel
Gas Code, ANSI Z223.1/NFPA 54.
Shown is suggested size of xed
bafe for different size risers.
Bafe Size (Inches)
Riser 8 10 12
A 6 8 10
Flue Connection And Venting - Continued
In certain cases where these short rises of less than 4
feet have been used, spillage of combustion products has
occurred at the draft-hoods farthest from the chimney.
Assuming the chimney is adequately sized, one acceptable
method to correct this spillage problem is to permanently
bafe the riser(s) closest to the chimney to reduce the
excess of room air entering those draft-hoods. DO NOT
BAFFLE ENOUGH TO CAUSE SPILLAGE. The use of xed
bafes in the short risers above the boiler draft-hood are
acceptable as spelled out in American National Standard
NFPA 54/ANSI Z223.1 National Fuel Gas Code, latest
revision.
Fabricate these xed bafes, using 20-gauge steel. See
Figure #6. Permanently attach the bafe to the inside of
the riser(s). Trial and error will dictate the degree to which
each should be positioned to avoid draft-hood spillage
at the far end of the boiler. Be careful to avoid bending
the xed bafe so it will obstruct the ue gas ow in the
horizontal collector.
VENT INSTALLATION
Figure 6
IMPORTANT: Extend chimneys at least 2 feet above any
object within radius of 15 feet, including roof.
Page view 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 35 36

Comments to this Manuals

No comments